عنوان المقالة:Thermodynamic Analysis of a Power Plant Waste Heat Driven Absorption Refrigeration System Thermodynamic Analysis of a Power Plant Waste Heat Driven Absorption Refrigeration System
احمد حسن احمد حسن | Ahmed Hassan Ahmed Hassan | 5625
نوع النشر
مؤتمر علمي
المؤلفون بالعربي
Mohamad Mehyo; Hakan Özcan; Ahmed Hassan Ahmed Hassan
المؤلفون بالإنجليزي
Mohamad Mehyo; Hakan Özcan; Ahmed Hassan Ahmed Hassan
الملخص العربي
Assessment of the exergetical and energical performance of a single-stage NH3–NaSCN absorption refrigeration system has carried out for the effective recovery of low-temperature waste heat of the drainage tanks in AL-Zara thermal power plant in Hama, Syria. Thermodynamic analysis, both first and second law, has employed to be a tool for consideration of the quantity and quality of energy in the thermal system. Exergy analysis has determined the destruction and losses of exergy in various components and hence in the overall system. The thermal properties, entropy, and exergy of the working mixture have also calculated to analyze irreversible loss in system components under operating conditions by MATLAB® computer program. The obtained numerical results for the cycle have tabulated where the coefficient of performance and the coefficient of performance for heating have reached up to 0.55, 1.55 respectivel y. The efficiencies of the second law of thermodynamics for cooling and heating applications have reached up to 0.295, 1.295 respectively
الملخص الانجليزي
Assessment of the exergetical and energical performance of a single-stage NH3–NaSCN absorption refrigeration system has carried out for the effective recovery of low-temperature waste heat of the drainage tanks in AL-Zara thermal power plant in Hama, Syria. Thermodynamic analysis, both first and second law, has employed to be a tool for consideration of the quantity and quality of energy in the thermal system. Exergy analysis has determined the destruction and losses of exergy in various components and hence in the overall system. The thermal properties, entropy, and exergy of the working mixture have also calculated to analyze irreversible loss in system components under operating conditions by MATLAB® computer program. The obtained numerical results for the cycle have tabulated where the coefficient of performance and the coefficient of performance for heating have reached up to 0.55, 1.55 respectivel y. The efficiencies of the second law of thermodynamics for cooling and heating applications have reached up to 0.295, 1.295 respectively
تاريخ النشر
16/08/2018
الناشر
avestia - The 4th World Congress on Mechanical, Chemical, and Material Engineering (MCM'18) - Madrid, Spain
رقم المجلد
رقم العدد
رابط DOI
https://doi.org/10.11159/htff18.106
الصفحات
HTFF 106
رابط خارجي
https://avestia.com/MCM2018_Proceedings/files/paper/HTFF/HTFF_106.pdf
الكلمات المفتاحية
Power Plant, Waste heat, Absorption Refrigeration, NH3–NaSCN, Exergy.
رجوع