عنوان المقالة: Experimental Validation of a Mitigation Method of Ferranti Effect in Transmission Line
طارق حسام فقها | Tareq Foqha | 1347
Publication Type
Journal
Arabic Authors
English Authors
tareq foqha, samer yassin alsadi, Shady S. Refaat, Kais Abdulmawjood
Abstract
Electric power transmission networks should be operated in efficient, safe, and reliable conditions. To improve the stability and transfer capability of power transmission, it is necessary to mitigate the Ferranti effect. This paper investigates the impact of increasing the length of the transmission line on its receiving end voltage under no-load conditions. A variable shunt reactor compensation for transmission lines is used to control the voltage level at different lengths of the transmission line. The proposed method demonstrates that the value of the shunt reactor required to maintain the receiving end voltage can be estimated. Moreover, the system is modeled using the PowerWorld simulator, and the effectiveness of the proposed model has been verified by experimental results. The experimental results demonstrate the efficiency of the proposed methodology and match the simulation results, which are then validated by simulating the WSCC 9-bus and IEEE 30-bus test systems.
Publication Date
1/28/2023
Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Volume No
11
Issue No
ISSN/ISBN
2169-3536
DOI
https://doi.org/10.1109/ACCESS.2023.3244826
Pages
15895
File Link
تحميل (0 مرات التحميل)
External Link
https://ieeexplore.ieee.org/document/10044097
Keywords
Transmission lines, Ferranti effect, shunt compensation, PowerWorld simulator